Copper rate 
21. November 2024
: upper CUN 
875,86
 EUR/100kg
KBE Elektrotechnik GmbH | Symeonstraße 8, 12279 Berlin | GERMANY
+49 (0)30 / 25 208-100

AWG table

AWG table - American strand construction

In the North American economic area, the dimensions of copper conductors for power and telecommunication purposes are mostly given in AWG (American Wire Gauge), whereas in Germany, Europe and many other parts of the world we speak of metric cross sections cross sections in mm². 
The following overview provides translation assistance for the individual cross-sectional areas:
AWG No.Outer diameter Ø mmCross section geometric mm²Conductor resistance Ohm/km
1000 MCM29.35070.036
90027.84560.04
75025.43800.048
60022.73040.061
55021.72790.066
50020.72530.07
45019.62280.08
40018.52030.09
35017.31770.1
300161520.12
25014.61270.14
4/011.68107.20.18
3/010.4850.23
2/09.2767.40.29
08.2553.40.37
17.3542.40.47
26.5433.60.57
35.8326.70.71
45.1921.20.91
54.6216.81.12
64.1113.31.44
73.6710.61.78
83.268.342.36
92.916.622.77
102.595.263.64
112.34.154.44
122.053.315.41
131.832.637.02
141.632.088.79
151.451.6511.2
161.291.3114.7
171.151.0417.8
181.0240.82323
190.9120.65328.3
200.8120.51934.5
210.7230.41244
220.6440.32454.8
230.5730.25970.1
240.5110.20589.2
250.4550.163111
260.4050.128146
270.3610.102176
280.3210.0804232
290.2860.0646282
300.2550.0503350
310.2270.04446
320.2020.032578
330.180.0252710
340.160.02899
350.1430.01611125
360.1270.01231426
370.1130.011800
380.1010.007952255
390.08970.006322860
400.0790.004873802
420.0640.003175842
440.0510.002039123
Alternatively for bigger cross sections in MCM 1 M.C.M. = 1000 Circ. Mils = 0,5067 mm²